Inverters & equipment

Disconnect switch sizing tool

Enter your inverter or array current. Get the required amperage with the NEC 125% factor applied and a recommended standard disconnect size, for both AC and DC.

Your numbers

1 Project details Optional
Shown on your exported report. Leave blank to skip.
2 AC disconnect
240V single-phase is standard for most US and Canadian residential systems.
3 DC disconnect Optional
Total combined string current, from the parallel strings current calculator or combiner box sizing calculator.

Try a different inverter size

Drag the slider to change the inverter AC output. The AC current, factored current, and recommended disconnect size update as you move it. The example keeps 240 V and 44 A of DC current, the same as the tool above.

7.6 kW
AC current
31.67 A
With 125% factor
39.58 A
AC disconnect
60 A
120 V
63.33 A
208 V
36.54 A
240 V
31.67 A
277 V
27.44 A
480 V
15.83 A
600 V
12.67 A

AC current equals inverter watts divided by 240 V. The NEC 125 percent factor is applied, then rounded up to the next standard size: 30, 60, 100, 200, or 400 A. The bars show the AC current at other service voltages for the inverter size you pick. The DC side stays at 44 A times 1.25, or 55.00 A, which also lands on a 60 A disconnect.

How it works

Three steps to your disconnect sizing

Step 1

Get your inverter's AC output rating

This comes straight from the inverter's nameplate or the grid tie inverter sizing calculator if you're still finalizing your inverter choice.

Step 2

Get your combined DC current if needed

If you also need a DC disconnect, pull the combined string current from the parallel strings current calculator or your combiner box sizing.

Step 3

Confirm local requirements

Some utilities and jurisdictions specify particular disconnect types, locations, or labeling requirements beyond just the amperage rating calculated here.

7.6 kW at 240 V: both disconnects land on 60 A

Hover or tap each part of the picture to see what it means.

INVERTER OUTPUT7.6 kWAC VOLTAGE240 VDC CURRENT44 A AC CURRENT31.67 A7,600 W / 240 Vinverter output current AC x 125%39.58 A31.67 A x 1.25NEC continuous factor DC x 125%55.00 A44 A x 1.25NEC continuous factor Both sides use the same 125% NEC continuous factor,but each rounds up to its own standard switch size. AC DISCONNECT60 ADC DISCONNECT60 ANEC FACTOR125%

Understanding disconnect switch sizing

Why disconnects exist as a distinct safety requirement

A disconnect switch gives utility workers, firefighters, and installers a clear, accessible point to fully de-energize a solar system for maintenance or in an emergency. Unlike a circuit breaker that's primarily there to protect wiring from overcurrent, a disconnect's main job is providing a definite, visible break in the circuit that anyone can confirm is open, which is why it's treated as a distinct code requirement rather than just another overcurrent device, in the same fire-and-life-safety spirit as the setback rules covered in the fire code setback loss calculator.

Why AC and DC disconnects are sized from different starting points

The AC disconnect sits on the inverter's output side and is sized from the inverter's AC current, calculated from its wattage rating and voltage. This tool leaves power factor out of that AC current figure. It divides watts by volts with no power factor step, while the AC cable loss tool does include power factor, so its current can read higher for the same inverter when power factor is below 1.0. The DC disconnect sits on the array's input side and is sized from the combined DC current of all strings feeding into it, following the same current logic used in the combiner box sizing calculator and parallel strings current calculator. These are genuinely separate calculations even though both apply the same 125% continuous factor, drawn from the same conductor ampacity limits in NEC Table 310.16, before rounding to a standard switch size.

How disconnects differ from a transfer switch

It's easy to conflate disconnects with transfer switches since both involve switching equipment in a solar installation, but they serve different purposes. A disconnect fully isolates a circuit, cutting power entirely. A transfer switch instead routes power between two active sources, like utility grid power and battery backup power, without necessarily de-energizing anything, the distinction covered in the transfer switch sizing calculator. Many systems need both, and confusing one for the other during planning can lead to missing a required piece of equipment.

Where disconnects typically get installed

A DC disconnect commonly sits at or near the inverter's DC input, sometimes integrated directly into the inverter itself on newer models. An AC disconnect typically sits near the utility meter or main service panel, in a location accessible to utility personnel without needing to enter the building. Exact placement requirements vary by local code and utility, so it's worth confirming before finalizing an installation plan, and the connector and wiring inspection cost estimator covers what it costs to keep the wiring at both locations in good shape over time.

What this tool doesn't cover

This calculator handles amperage sizing only. Disconnects also need a voltage rating that matches or exceeds the system's operating voltage, and some jurisdictions specify additional requirements like a lockable, visible-break design, similar to the compliance details in the rapid shutdown compliance cost estimator. Always cross-check the final product selection against your local electrical code and installer's recommendation, or start with the Solar Energy Industries Association's plain-language solar overview if you're new to how this equipment fits into the bigger picture.

Questions

Frequently asked

Divide the inverter's AC output in watts by the voltage to get current, multiply by 1.25 for the NEC continuous load factor, then round up to a standard disconnect size. A 7.6kW inverter at 240V draws about 31.7A, which becomes 39.6A after the factor and rounds up to a 60A disconnect. This current figure leaves power factor out.

An AC disconnect isolates the inverter's AC output from the electrical panel and grid, while a DC disconnect isolates the solar array's DC output from the inverter. Both serve as safety isolation points, but they're rated for different current and voltage characteristics on either side of the inverter.

No. A disconnect switch is a safety isolation device that fully de-energizes a circuit for maintenance or emergency shutoff. A transfer switch routes power between two sources, like the grid and a backup system, and doesn't necessarily de-energize anything on its own.

Most residential installations require both a DC disconnect near the array or at the inverter's DC input, and an AC disconnect near the utility meter or main panel, though some inverters include an integrated DC disconnect. Local code and utility interconnection requirements determine the exact configuration needed.