Battery & storage

Battery sizing without solar recharge

Enter your load and outage duration. See the most conservative battery size, assuming zero solar or grid input for the entire period.

Your numbers

1 Project details Optional
Shown on your exported report. Leave blank to skip.
2 Load and duration
The full length of the outage, with zero recharge assumed throughout.
3 Battery characteristics

Try a different outage length

The same 600 W load and 13.5 kWh battery size at 90 percent depth of discharge and 92 percent round trip efficiency as the tool above. Drag the slider to change the outage hours.

72 hours
Batteries needed
4
Nameplate size
52.17 kWh
Usable energy
43.20 kWh
200 W load
17.39 kWh
400 W load
34.78 kWh
600 W load
52.17 kWh
800 W load
69.57 kWh
1,000 W load
86.96 kWh
1,500 W load
130.43 kWh

Maths: usable energy is the load in kW times the outage hours. Nameplate capacity is usable energy divided by 90 percent depth of discharge times 92 percent round trip efficiency. Battery count rounds the nameplate size up to whole 13.5 kWh batteries. The example load is 600 W, as in the tool above.

How it works

Three steps to zero-recharge sizing

Step 1

Confirm this is really your scenario

Zero recharge applies if you have no solar, unconnected solar, or unreliable sun exposure. If you have solar wired for backup, the with solar recharge tool is likely more realistic. The NREL's solar resource data publishes the reference data behind this estimate.

Step 2

Enter your full outage duration

This is the entire window with zero input, not just an overnight bridge.

Step 3

Consider trimming loads instead of scaling batteries

At this scale, a smaller load list is often more cost-effective than adding batteries. The critical loads calculator can help.

Zero recharge means storing all 3 days up front

Hover or tap each part of the picture to see what it means.

Load600 W Outage72 hours Usableenergy43.2 kWh Nameplate52.2 kWh BATTERIES4 WITH DAILY RECHARGE1

Understanding zero-recharge battery sizing

Why this is the most conservative planning scenario

Sizing without any solar or grid recharge assumes the battery has to store every kWh needed for the entire outage duration upfront, with nothing added back in until grid power returns. This produces the largest, most expensive battery figure of any sizing approach on this site, since it makes no assumptions about favorable weather, working equipment, or a connected solar array. Use it when those assumptions genuinely don't apply to your situation, not as a default starting point if you do have working solar backup.

When zero-recharge sizing is the realistic choice, not just the cautious one

Homes without any solar installation, solar systems that aren't wired through a backup gateway to stay connected during an outage, a distinction the Department of Energy's inverter basics guide explains as a safety requirement for grid-tied systems, and locations with historically unreliable sun exposure during typical outage season, tracked in NREL's solar resource data, are all situations where zero-recharge sizing reflects genuine reality rather than excessive caution. The with solar recharge tool is the better starting point if none of these apply to you.

The middle ground most installers actually recommend

Few real installations size purely to one extreme or the other. Many installers instead size somewhere between the two, assuming partial rather than full daily solar recharge to account for less-than-ideal weather during an actual outage, producing a battery size larger than the optimistic full-recharge figure but smaller than this fully conservative zero-recharge figure, a middle ground the inverter itself also needs to support, as covered in the off-grid inverter sizing calculator in our Inverters & Equipment category. Comparing both extremes side by side, using this tool and the battery storage size calculator together, helps calibrate where a reasonable middle ground sits for your specific situation.

What to do with this number next

If this zero-recharge figure feels too large to be practical, the critical loads calculator can help trim your load list down, or the charge time from grid tool shows what a connected solar system would change about this math. The quick financing comparison tool in our Financing category helps weigh whether this larger, more conservative figure still fits your budget.

Questions

Frequently asked

A 600 watt load over a 72 hour outage needs about 52.2 kWh of nameplate capacity with zero recharge assumed, roughly 4 batteries, compared to just 1 battery for the same load sized with daily solar recharge included.

No solar array installed, a solar array that isn't wired to the battery through a backup gateway, or a location with unreliable sun exposure during outage season are all situations where zero-recharge sizing is the realistic, not just conservative, choice.

Some installers still recommend at least partial zero-recharge sizing as a safety margin, even with solar present, to protect against extended cloudy stretches or unexpected equipment issues with the solar-to-battery connection. It's a matter of risk tolerance rather than a strict requirement.

Yes, many installers size somewhere between the two extremes, assuming partial rather than full daily solar recharge to account for less-than-ideal weather. This produces a battery size larger than the optimistic full-recharge figure but smaller than the fully conservative zero-recharge figure.